What causes cracks in a concrete floor?
Concrete floor cracks have many causes, from natural shrinkage of screed or concrete to structural problems such as a slab carrying more bending than it can take or soil settling beneath it. What separates the causes is the pattern, location and width of the cracks when they are plotted on a plan against the columns and beams.
← Scroll to see the full table →
| Crack pattern | Usual cause | What to do next |
|---|---|---|
| Grid / map cracking in the top screed | Shrinkage of the screed or concrete topping | Measure the width and track whether it grows |
| Parallel to a beam, top surface near the beam | Negative bending over the beam where the slab spans or hangs from it | Structural check by an engineer |
| Diagonal, radiating from a column or footing corner | Differential settlement or shear around the column | Structural check by an engineer |
| Gap between slab edge and wall or column | Soil under the slab settled while the piled structure did not | Core the slab to check for voids |
Classifying by pattern is only a starting point; the same pattern can have different causes, so it must be confirmed with further checks such as cores and crack monitoring over time. For cracks across a whole building, see which structural cracks are dangerous.
How do you survey floor cracks and prepare a crack map?
A crack map turns “cracks you can see” into “data you can check again later”. The steps SPN uses on site are:
- Divide the floor into bays by column and beam lines: name each bay by its column lines, for example “bay 2–6”, so every point has a clear reference.
- Walk the whole floor and number the points: choose representative cracks in every bay so the survey covers them all.
- Measure positions from the column lines: record offsets in two directions, for example “line 2 +2.4 m / line B +8.9 m”.
- Photograph against a tape measure: one wide shot to show the location and close-ups with the tape across the crack; in the case study three photos were taken per point.
- Measure the width with a crack gauge: read the widest part of the crack and note its direction, length and form (straight, grid, branching).
- Plot the map and summarise in a table: put every point on the plan with the beams, columns and other test locations to see whether the cracks are local or widespread.
Case study: a 23-point crack map on a ground floor more than 140 m long
This is a real SPN job from 2026 (the building and its original drawings are not disclosed). The ground floor of an old 5-storey building in Bangkok was being converted into usable space. The slab runs the full length of the building, with ground beams on piles every 12 m. The SPN team surveyed 23 crack points covering 12 floor bays, together with 13 concrete cores, 10 rebound hammer points and checks of the soil below. The crack map below was redrawn by SPN showing only the column lines, beams and survey points.
What does the crack map show?
The first thing the map shows is that the cracks are not concentrated in one place but spread through every bay along the whole building. They are straight cracks crossing in a grid plus branching cracks in the top screed, mostly wider than 2 mm. This pattern says the problem is not local damage, such as a heavy object being dropped, but the behaviour of the whole slab, so the next step was to look under the floor.
← Scroll to see the full table →
| Floor bay (column lines) | Crack points | Core results in the same bay |
|---|---|---|
| 1–2 | 18, 19 | No cores |
| 2–6 | 1, 2, 3 | 5 cores, upper concrete 0.20–0.37 m, void 0.08–0.45 m |
| 6–10 | 4 | No cores (3 rebound hammer points) |
| 10–14 | 17 | No cores |
| 14–18 | 5, 6, 7 | 1 core, concrete 0.20 m, void 0.15 m |
| 18–22 | 8, 9, 10 | 5 cores, concrete 0.22–0.34 m, void 0.05–0.13 m |
| 22–26 | 11, 12 | 1 core, concrete 0.19 m, void 0.06 + 0.05 m |
| 26–30 | 13, 14 | 1 core, concrete 0.26 m, void 0.14 m |
| 30–34 | 15, 16 | No cores |
| 34–38 | 20 | No cores |
| 38–42 | 21 | No cores |
| 42–46 | 22, 23 | No cores |
Set against the crack map, every bay that was cored had a void under the slab 0.05–0.45 m high, and none of the 13 cores contained reinforcement. The report therefore assessed that the cracks may be related to settlement of the soil under the slab, which reduces the continuity of the slab. Core results, strengths and the 3D model calculation are covered in existing concrete floor inspection: what to check.
Site photos of cracks from each floor bay
The photos below are taken from survey points in different bays, each with a tape measure for scale. The cracks include both straight cracks crossing in a grid and branching cracks, and they run from one end of the building to the other.
After finding floor cracks, what else should be checked to find the cause?
A crack map shows “what happens at the surface”, but finding the cause needs to know “what is underneath”. In the case study the SPN team followed up on the same days with:
- Concrete coring (ASTM C42/C42M): thickness, layering, reinforcement and voids under the slab; see what a concrete core test is.
- Rebound hammer (ASTM C805/C805M): surface hardness and uniformity between points; see what a rebound hammer test is.
- Kunzelstab and hand auger through the core holes: whether the soil below is dense or soft, with samples for testing; see the Kunzelstab Penetration Test (KPT).
How wide does a floor crack have to be before it is a concern?
There is no single number for every case. For reinforced concrete under service loads in dry air, ACI 224R-01 gives about 0.016 in., or 0.41 mm, as a reasonable crack width, and recognises that some cracks can grow wider over time. It is a useful reference, but always read it together with other factors:
- Trend over time: a crack that is getting wider or longer is more worrying than a wide crack that has stopped; track it with a crack gauge or crack meter.
- Location relative to the structure: cracks near beams, columns or slab edges are read differently from cracks mid-panel.
- Other symptoms: settlement, sagging, a hollow sound or a gap at the slab edge point to a problem under the floor.
- Which layer is cracked: in the case study most cracks wider than 2 mm were in unreinforced screed toppings, so their width did not directly show the slab strength, but it did mean the floor had to be checked from below.
What should you do if you find floor cracks?
- Do not fill or skim them yet: covering cracks before the cause is known makes it impossible to tell whether they are still growing.
- Photograph them against a tape and note the date: mark the crack ends with a pen to see whether they lengthen.
- Reduce load on that part of the floor: avoid heavy or concentrated loads such as document shelving, safes or machinery until the cause is known.
- Have an engineer survey and map the cracks: with cores where voids or settlement are suspected, so the repair matches the cause.
If the floor is to be renovated or change use, its load capacity should be assessed too; see how it is proven with real loads in what a floor load test is.
How long does a floor crack survey take and what does it cost?
It depends on floor area, number of points and the other tests done alongside. In the case study the survey of 23 crack points was carried out together with concrete coring, rebound hammer testing and soil checks under the slab, taking 3 days on site. The results were issued in a report certified by a licensed civil engineer (Council of Engineers Thailand) with signature and registration number.
For pricing, send crack photos or a plan via LINE @spnth or request a free quote within 24 hours. Prices exclude travel and equipment mobilisation, which are charged by distance to site. See all services on our non-destructive testing and structural inspection page.
Summary
Concrete floor cracks tell you more than they seem to. Recorded systematically on a crack map referenced to the columns and beams, with tape-measure photos and measured widths, they show whether a problem is local or affects the whole slab.
In the case study, a 23-point crack map spread across all 12 bays led to coring, which found a void under the slab at every core. The lesson: do not fill cracks before the cause is known, and when cracks run across the whole floor, have an engineer check what is underneath.